Daily Monitoring
Routine monitoring is recommended to be carried out in accordance with Table 13.2.
Table 13.2 Recommended Items for Routine Monitoring
| Item | Class 100 | Class 10 000 | Class 100 000 | Class 300 000 | Notes | |
|---|---|---|---|---|---|---|
| Bacterial concentration | Evaluation standard | Not exceeding management requirements | Not exceeding management requirements | Not exceeding management requirements | Not exceeding management requirements | At necessary locations or representative points |
| Bacterial concentration | Frequency of measurement Air | Frequent monitoring or once per operation | Once every 1~2 days | Once/week | times/month | At necessary locations or representative points |
| Bacterial concentration | Frequency of measurement Surface | Once per shift per day, 3 samples | Once a week, 3 samples | Once every 2 weeks, 3 samples | Once a month, 3 samples | At necessary locations or representative points |
| Bacterial concentration | Frequency of measurement 5 fingers of glove | 1 person/day | 1 person/1~2 days | 1 person/week | Measured according to the standard disinfection method | |
| Pressure difference | Evaluation standard | Not lower than the permissible lower limit and preferably not higher than 30Pa (except for biosafety cleanrooms); if lower than the permissible lower limit, adjustment should be made | Not lower than the permissible lower limit and preferably not higher than 30Pa (except for biosafety cleanrooms); if lower than the permissible lower limit, adjustment should be made | Not lower than the permissible lower limit and preferably not higher than 30Pa (except for biosafety cleanrooms); if lower than the permissible lower limit, adjustment should be made | Not lower than the permissible lower limit and preferably not higher than 30Pa (except for biosafety cleanrooms); if lower than the permissible lower limit, adjustment should be made | Measured by the differential pressure gauge on the wall at the doorway |
| Pressure difference | Frequency of measurement | Once/day | Once/day | Once/week | Once/week | Measured by the differential pressure gauge on the wall at the doorway |
| Air volume | Evaluation standard | Not lower than management requirements | Not lower than management requirements | Not lower than management requirements | Not lower than management requirements | Measured on rest days or during major overhaul; for rooms below Class 100, convert the air outlet velocity into the air change rate; for Class 100 rooms, it is the cross-sectional velocity in the working zone |
| Air volume | Frequency of measurement | Once/half year | Once/half year | Once/year | Once/year | Measured on rest days or during major overhaul; for rooms below Class 100, convert the air outlet velocity into the air change rate; for Class 100 rooms, it is the cross-sectional velocity in the working zone |
| Cleanliness class | Evaluation standard | Not lower than management requirements | Not lower than management requirements | Not lower than management requirements | Not lower than management requirements | With instruments; without instruments, have a specialized institution measure it |
| Cleanliness class | Frequency of measurement | Frequent monitoring | Frequent monitoring | Frequent monitoring | Frequent monitoring | With instruments; without instruments, have a specialized institution measure it |
| Cleanliness class | Frequency of measurement | Once/year | Once/year | Once/year | Once/year | With instruments; without instruments, have a specialized institution measure it |