Mandatory Provisions Related to This Chapter
8.3.1 1 The clean operating department must ensure the reliability of power supply. When it is difficult to adopt dual power supply sources, a backup power source shall be provided, capable of automatic switchover within 1min
2 Power consumption in clean operating rooms shall be separated from that of auxiliary rooms, and the main feeder line of each operating room must be laid separately
8.3.2 4 Wireless communication equipment is prohibited in clean operating rooms
8.3.4 2 Cardiac surgery operating rooms must be provided with a functional grounding system equipped with an isolation transformer