Project Overview
| Project | Ultra-Clean Modern Digital Operating Room Construction Project |
|---|---|
| Hospital | PLA Joint Logistic Support Force 988th Hospital |
| Project Date | August 2024 |
| Room Type | Modern digital clean operating room with a laminar-flow supply ceiling |
| Cleanliness Design Intent | Class 100 / Class 10,000 cleanroom conditions; formal classification is determined by commissioning and acceptance testing |
| Principal Integration | Cleanroom wall and flooring systems, LED lighting, medical pendants, surgical lights, operating table, digital controls and built-in medical cabinetry |
Project Bill of Materials (BOM)
The following 18-item BOM covers the cleanroom enclosure, core operating-room equipment, wall-integrated cabinets and controls, medical-gas and electrical terminals, and operating-room doors for the approximately 40 m² standard operating room. The document corresponds to Version 2.0 (Final Spec).Procurement note: The medical pendants (monitoring/anesthesia and surgical pendants), operating table, and surgical shadowless light were procured by the client.
Download English BOM PDF (18 Items)| No. | Item Name | Specifications & Technical Parameters | Unit | Qty | Remarks / Location |
|---|---|---|---|---|---|
| I. CLEANROOM ENCLOSURE & STRUCTURAL FINISHES | |||||
| 1 | Wall Panel System | 1.0 mm electro-galvanized steel panel with antibacterial coating, framework-free quick-install system with aluminum profile connectors. | sqm | 115 | Four perimeter walls, direct wall-mount, incl. R-curved corner profiles. |
| 2 | Ceiling System | Modular metal cleanroom ceiling panels with dust-proof seals and seamless joint fittings. | sqm | 42 | Cleanroom ceiling area excluding laminar airflow ceiling. |
| 3 | Cleanroom Light Fixtures | Recessed dust-free LED bevel lighting panel (600 × 1200 mm, IP65 rated, color temp 4500 K, anti-glare). | set | 8 | Flush ceiling mounted surrounding central laminar area. |
| 4 | Laminar Airflow Ceiling | Class III / II Clean Air Supply Canopy (2.4 m × 1.2 m / 2.6 m × 1.4 m) with integrated H14 HEPA filtration box. | set | 1 | Mounted directly above central surgical table. |
| 5 | Return Air Grille | Stainless steel (SUS304) side-wall return air grille with built-in air volume control damper and flame-retardant mesh. | set | 4 | Installed at bottom four corners / side wall locations. |
| 6 | HEPA Filters | H14 mini-pleat HEPA filter (Efficiency 99.995% @ 0.3 μm particle size). | pcs | 6 | Fitted within laminar airflow ceiling and duct terminals. |
| II. MEDICAL CEILING PENDANTS & CORE EQUIPMENT | |||||
| 7 | Monitoring Pendant | Dual-arm high-strength aluminum medical pendant (arm radius 800 + 800 mm), equipped with shelves, monitor tray, and gas/electric outlets. | set | 1 | Positioned at head/left side of surgical table. Client-procured. |
| 8 | Surgical Pendant | Single-arm aluminum surgical pendant %LS Related ProductsRelated posts | |||